Anechoic Chamber Professional Maker
RF Anechoic Chamber (RF/EMC Chamber)
10m Semi Anechoic Chamber
5m Semi Anechoic Chamber
3m Semi Anechoic Chamber (966)
844 Shielded Room for RS Chamber
Pre-test 743 Semi Anechoic Chamber
Fully Anechoic Chamber
Open Area Test Site
Customized Anechoic Chamber
Semi Anechoic Chamber SAC 3M
No
Item
Description
QTY.
Unit
Major structure
1
PAN Type Modules
Outside dimension 9.0x 6.0 x 6.0m(apx.)
1
SET
The galvanized steel module is 2mm thick and product surface painting
Braid shielded and anti-slip screw
2
Steel Structure
H-Beam for five wall and insulating floor
1
SET
3
Ground System
Ground rod have a safe electrical system, near power filter
1
SET
4
Shielding Door
KT 1.2M*2M electric control swing type shielding door
1
SET
Can open manual inside/outside
Warning lamp
5
Air Vents
Waveguide air vents 300mm*300mm
6
PC
6
Power Line Filter
2x32A, Insertion Loss: >100dB, 14kHz~40GHz,
4
PC
7
Connector Panels
AP: N*2、SMA*2、50mm pipe *1
1
SET
CP:depend on design drawing
Absorber Materials
8
Anechoic Absorber Materials & Ferrite
Emerson & Cuming (E&C) EPP on four side wall and ceiling.
Floor : partially absorber
1
SET
9
White Cap
Make up panel (Cap type) – used non flammable material
1
SET
Control System
10
Antenna Tower
Bore sight antenna mast 1 ~ 4m lifting
1
SET
Resolution : 1cm
Lifting speed : 10 ~ 150mm/Sec
11
Turntable
Medium duty turntable–2m diameter with a 1,500 Kg weight capacity
1
SET
Rotation speed: 1-12 degree/sec
Positioning accuracy : ± 1 degree
Rotation range : +365 degree~-5 degree
Provide drain pipe for the washing machine
12
Controller
for Antenna tower and Turntable
1
SET
Can control IEEE-488.2 Bus antenna tower and turntable
Fiber connect control
13
Anechoic test table
180Lx120Wx80H cm, Tabletop made of PES
1
SET
CCTV System
14
CCTV System
32 X zoom camera and high definition record
One is monitoring chamber, the other is monitoring DUT
Exception handling and recording
1
SET
15
Projector
Non-interference monitor and rojector for debug
1
SET
Setting under floor
Monitor and rojector interference source is lower than chamber base
Illumication System
16
Illumication
Lifting LED will easy to maintenance (including controller)
6
SET
17
Drainage System
Drainage system for washing machine
1
SET
Shielding Room for test facility control of SAC 3M
No
Item
Description
QTY.
Unit
1
PAN Type Modules
Outside dimension 3.0 x 3.0 x 3.0 m(Apx.)
1
SET
13cm raised floor, placeholder for drain pipe
The galvanized steel module is 2mm thick and product surface painting
Braid shielded and anti-slip screw
2
Ground System
Ground rod have a safe electrical system, near power filter
1
SET
3
Shielding Door
KT 1.2M*2M manual control swing type shielding door
1
SET
4
Air Vents
Waveguide air vents 300mm*300mm
4
PC
6
Power Line Filter
2x32A, Insertion Loss: >100dB, 14kHz~40GHz,
1
PC
7
Connector Panels
AP: N*2、SMA*2、50mm pipe *1
1
SET
CP:depend on design drawing
8
Anechoic Testing
Anechoic Testing follow EN50147-1(Latest)
10 KHz ≧ -60dB
100 KHz≧ -80 dB
1MHz ~ 18GHz ≧ -100dB1
SET
9
Construction
According to the drawings and accommodation
1
SET